19, Jalan Perdana 10/12,
Taman Pandan Perdana,
55300 Kuala Lumpur,
Malaysia.
+603-9274 4011
+603-9274 4099
Previous | 1 / 3 | Next |
Current | |
---|---|
Range | 6 x 0~15A |
Power(typical) |
6x 150VA at 15A 3 x 240VA at 30A |
Accuracy (typical) | <0.08% rd+0.02% rg.guar., at 0~15A |
Voltage | |
Range | 4 x 0~300V |
Power(typical) |
4x 75VA at 300V 3 x 100VA at 300V |
Accuracy (typical) | <0.08% rd+0.02% rg.guar., at 0~300V |
Frequency | |
Sine signal | 1 … 1000Hz |
Transient signal | dc … 10.0kHz |
Accuracy | 0.3ppm |
Phase angle | |
Range | -360°~+360º |
Accuracy (typical) | 0.05º |
Auxiliary DC supply | 0~300V |
Power |
88W at 110V, 176W at 220V, 90W at 300V |
Binary input | |
Number | 8 |
Type | 0-400Vdc threshold or potential free |
Counter input | |
Number | 4 |
Sample rate | 20kHz |
Binary output | |
Number | 4 |
Type | Relay |
Number | 4 |
Type | Semiconductor |
Low level output | |
Number | 12 |
Accuracy (typical) | 0.025% |
DC measurement | |
Voltage measuring | 0…±10V |
Current measuring | 0...±20mA |
IEC61850 GOOSE | optional |
Dimension | 360*157*367mm |
Weight | 20kg |